Permit: T09CM00795
Permit Details
Apply Date:
04/07/2009
Applicant:
N/A
Description:
PARK IMPROVEMENTS:RETAINING WALLS L 30" TO 5' LIGHT POLES 30' HIGH - MULTIUSE PATH
Contractors:
- SAFETY QUALITY PRODUCTIVITY CONSTRUCTION
Outstanding Activity Conditions
Permit Number - T09CM00795
Permit Status: Expired
Permit Description: PARK IMPROVEMENTS:RETAINING WALLS L 30" TO 5'
LIGHT POLES 30' HIGH - MULTIUSE PATH
Total Outstanding Activity Conditions - 5
| Date | Name |
|---|---|
| 04/07/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
| 05/26/2009 | SPECIAL INSPECTION FORMS AND REPORTS REQUIRED PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY. |
| 05/26/2009 | SPECIAL INSPECTION FOR CONCRETE IS REQUIRED.. |
| 05/26/2009 | SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED. |
| 05/26/2009 | SPECIAL INSPECTION FOR PILING, DRILLED PIERS AND CAISSONS IS REQUIRED. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09CM00795
Permite Description: PARK IMPROVEMENTS:RETAINING WALLS L 30" TO 5'
LIGHT POLES 30' HIGH - MULTIUSE PATH
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| BUILDING - PROGRESS | N/A | Not Inspected | ||
| 06/29/2011 | BUILDING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* 1) NEED DBL STAMPED SPECIAL INSPECTION CERT 2) NEED ELECTRIC, FIRE AND ENGINEERING FINALS 3) HAVE ACTIVITY CARD ON SITE |
| 08/05/2010 | STEM WALL/RETAINING WALL | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 09/01/2010 | EXCAVATION/LAYOUT REBAR & ZON | N/A | Partial Approval | IVRS - Inspection :* 1) BLANCE OF LIGHT POLE BASES ON COUNTRY CLUB SIDE |
Completed Inspections
Permit Status: Expired
Permit Number: T09CM00795
Permit Description: PARK IMPROVEMENTS:RETAINING WALLS L 30" TO 5'
LIGHT POLES 30' HIGH - MULTIUSE PATH
Total Completed Inspections - 8
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED FOR "NEW STEEL POLE/DISCONNECT AT "PICNIC PLACE" ENTRANCE EAST OF COUNTRY CLUB, NORTH OF 22ND ST |
| 11/10/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED FOR "LIGHTING PEDESTAL" PER R. HOLLANDER |
| 12/27/2010 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* 1) SOUTH PEDESTAL LISTED AND LABELED AS "SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT"-THIS IS A SUB PANEL TO MAIN DISCONNECTION POLE 2) STILL NEED REJECTION PINS AT MAIN DISCONNECT FOR R TYPE FUSES 3) CONDUCTOR #8 AND LARGER IN RACEWAYS TO BE STRANDED 310.3 4) OK ALL POLES MAKE UP EXCEPT 2 IN FRONT OF BALL PARK WEST END OF PARKING LOT |
| 12/27/2010 | OUTDOOR LIGHTING FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 06/29/2011 | FIRE - FINAL | WMOTTO | Approved | |
| 12/01/2011 | ELECTRIC - OUTDOOR LIGHTING | DSANTACR | Approved | IVRS - Inspection :* |
| 12/01/2011 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
| 12/01/2011 | ELECTRIC - UFER | DSANTACR | Approved | IVRS - Inspection :* |