Permit: T09CM00795

Parcel: 12620001C


Addresses:

900 S RANDOLPH WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/01/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/29/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SEE NOTES INSPECTION #1 110.26
06/28/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ELECTRIC CONTRACTOR HAS KEYS TO LOCKS FOR ELECTRIC EQUIPMENT
12/27/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SOUTH PEDESTAL LISTED AND LABELED AS "SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT"-THIS IS A SUB PANEL TO MAIN DISCONNECTION POLE
2) STILL NEED REJECTION PINS AT MAIN DISCONNECT FOR R TYPE FUSES
3) CONDUCTOR #8 AND LARGER IN RACEWAYS TO BE STRANDED 310.3
4) OK ALL POLES MAKE UP EXCEPT 2 IN FRONT OF BALL PARK WEST END OF PARKING LOT
11/10/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :
See detailed listing on site.| 999*
1) MUST HAVE DISCONNECT LOCKED IN OFF POSITION WHEN NOT BEING WORKED ON
11/09/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
IRGG:
1) NO LOAD COMNECTION AT IRRIGATION SERVICE
2) NO FUSES OR "R" PINS
3) VERIFY 2ND GROUND ROD
4) LIGHTING PEDESTAL HAS BEEN REPLACED WITH A CORRECTLY LABELED UNIT
10/29/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/27/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*