Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM00795
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/29/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SEE NOTES INSPECTION #1 110.26 |
|
06/28/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ELECTRIC CONTRACTOR HAS KEYS TO LOCKS FOR ELECTRIC EQUIPMENT |
|
12/27/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SOUTH PEDESTAL LISTED AND LABELED AS "SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT"-THIS IS A SUB PANEL TO MAIN DISCONNECTION POLE 2) STILL NEED REJECTION PINS AT MAIN DISCONNECT FOR R TYPE FUSES 3) CONDUCTOR #8 AND LARGER IN RACEWAYS TO BE STRANDED 310.3 4) OK ALL POLES MAKE UP EXCEPT 2 IN FRONT OF BALL PARK WEST END OF PARKING LOT |
|
11/10/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST HAVE DISCONNECT LOCKED IN OFF POSITION WHEN NOT BEING WORKED ON |
|
11/09/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* IRGG: 1) NO LOAD COMNECTION AT IRRIGATION SERVICE 2) NO FUSES OR "R" PINS 3) VERIFY 2ND GROUND ROD 4) LIGHTING PEDESTAL HAS BEEN REPLACED WITH A CORRECTLY LABELED UNIT |
|
10/29/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/27/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |