Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T09CM00795
Permit Details
Apply Date:
04/07/2009
Applicant:
N/A
Description:
PARK IMPROVEMENTS:RETAINING WALLS L 30" TO 5' LIGHT POLES 30' HIGH - MULTIUSE PATH
Contractors:
- SAFETY QUALITY PRODUCTIVITY CONSTRUCTION
Permit Reviews
Permit Number - T09CM00795
Permit Status: Expired
Permit Description: PARK IMPROVEMENTS:RETAINING WALLS L 30" TO 5'
LIGHT POLES 30' HIGH - MULTIUSE PATH
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
03/24/2010 | REVISION - - 1ST | 03/24/2010 | COMPLETED |
04/07/2009 | PLANS OK TO SUBMIT - COMM | 04/07/2009 | COMPLETED |
04/07/2009 | PLANS OK TO SUBMIT - SITE | 04/07/2009 | COMPLETED |
04/07/2009 | SITE | 05/06/2009 | COMPLETED |
04/07/2009 | COMMERCIAL NEW | 05/06/2009 | COMPLETED |
04/15/2010 | REVISION - - 2ND | 04/16/2010 | COMPLETED |
05/22/2009 | RESUBMITTAL - SITE | 06/12/2009 | COMPLETED |
05/22/2009 | RESUBMITTAL | 06/12/2009 | COMPLETED |
06/15/2009 | RESUBMITTAL - SITE ALL | 12/18/2009 | COMPLETED |
06/15/2009 | RESUBMITTAL | 12/18/2009 | COMPLETED |
07/09/2010 | REVISION - - 3RD | 07/09/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09CM00795
Permit Status: Expired
Permit Description: PARK IMPROVEMENTS:RETAINING WALLS L 30" TO 5'
LIGHT POLES 30' HIGH - MULTIUSE PATH
Total Outstanding Activity Conditions - 5
Date | Name |
---|---|
04/07/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
05/26/2009 | SPECIAL INSPECTION FORMS AND REPORTS REQUIRED PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY. |
05/26/2009 | SPECIAL INSPECTION FOR CONCRETE IS REQUIRED.. |
05/26/2009 | SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED. |
05/26/2009 | SPECIAL INSPECTION FOR PILING, DRILLED PIERS AND CAISSONS IS REQUIRED. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09CM00795
Permite Description: PARK IMPROVEMENTS:RETAINING WALLS L 30" TO 5'
LIGHT POLES 30' HIGH - MULTIUSE PATH
Total Outstanding Inspections - 4
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
BUILDING - PROGRESS | N/A | Not Inspected | ||
06/29/2011 | BUILDING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* 1) NEED DBL STAMPED SPECIAL INSPECTION CERT 2) NEED ELECTRIC, FIRE AND ENGINEERING FINALS 3) HAVE ACTIVITY CARD ON SITE |
08/05/2010 | STEM WALL/RETAINING WALL | N/A | Not ready for Inspection | IVRS - Inspection :* |
09/01/2010 | EXCAVATION/LAYOUT REBAR & ZON | N/A | Partial Approval | IVRS - Inspection :* 1) BLANCE OF LIGHT POLE BASES ON COUNTRY CLUB SIDE |
Completed Inspections
Permit Status: Expired
Permit Number: T09CM00795
Permit Description: PARK IMPROVEMENTS:RETAINING WALLS L 30" TO 5'
LIGHT POLES 30' HIGH - MULTIUSE PATH
Total Completed Inspections - 8
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED FOR "NEW STEEL POLE/DISCONNECT AT "PICNIC PLACE" ENTRANCE EAST OF COUNTRY CLUB, NORTH OF 22ND ST |
11/10/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED FOR "LIGHTING PEDESTAL" PER R. HOLLANDER |
12/27/2010 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* 1) SOUTH PEDESTAL LISTED AND LABELED AS "SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT"-THIS IS A SUB PANEL TO MAIN DISCONNECTION POLE 2) STILL NEED REJECTION PINS AT MAIN DISCONNECT FOR R TYPE FUSES 3) CONDUCTOR #8 AND LARGER IN RACEWAYS TO BE STRANDED 310.3 4) OK ALL POLES MAKE UP EXCEPT 2 IN FRONT OF BALL PARK WEST END OF PARKING LOT |
12/27/2010 | OUTDOOR LIGHTING FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
06/29/2011 | FIRE - FINAL | WMOTTO | Approved | |
12/01/2011 | ELECTRIC - OUTDOOR LIGHTING | DSANTACR | Approved | IVRS - Inspection :* |
12/01/2011 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
12/01/2011 | ELECTRIC - UFER | DSANTACR | Approved | IVRS - Inspection :* |