Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
10/01/2009
Applicant:
OLYMPIC WEST FIRE PROTECTION COR
Description:
Install 17 fire sprinklers
Contractors:
  • OLYMPIC WEST FIRE PROTECTION COR

Outstanding Activity Conditions

Permit Number - T09BU01478
Permit Status: Final
Permit Description: Install 17 fire sprinklers
Total Outstanding Activity Conditions - 1
Date Name
10/01/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09BU01478
Permit Description: Install 17 fire sprinklers
Total Completed Inspections - 3
Date Description Inspector Results Comments
10/21/2009 FIRE SPKLR - FINAL CSCHULTZ Approved NEED AS BUILTS, RISER DETAIL ON PLANS DIFFERENT THEN WHAT IS ON SITE. RISER SHALL HAVE 2 GAUGES ONE ON SUPPLY SIDE AND ONE ON SYSTEM SIDE PER 2002 NFPA 13R SEC. 6.6.5 AND NFPA 13 SEC. 7.1.1.
NO FDC IS NEEDED IF THE BUILDING IS LESS THAN 2000 SQUARE FEET PER 2002 NFPA 13R 6.6.4.1
10/21/2009 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved 200 PSI FOR 2 HOURS
NEED AS BUILTS, RISER DETAIL ON PLANS DIFFERENT THEN WHAT IS ON SITE. RISER SHALL HAVE 2 GAUGES ONE ON SUPPLY SIDE AND ONE ON SYSTEM SIDE PER 2002 NFPA 13R SEC. 6.6.5 AND NFPA 13 SEC. 7.1.1.
NO FDC IS NEEDED IF THE BUILDING IS LESS THAN 2000 SQUARE FEET PER 2002 NFPA 13R 6.6.4.1
01/25/2010 PERMIT FINALED CSCHULTZ Approved