Permit: T09BU01478

Parcel: 10712225A

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T09BU01478

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2009 FIRE SPKLR - OH PIPING & HYDRO Approved 200 PSI FOR 2 HOURS
NEED AS BUILTS, RISER DETAIL ON PLANS DIFFERENT THEN WHAT IS ON SITE. RISER SHALL HAVE 2 GAUGES ONE ON SUPPLY SIDE AND ONE ON SYSTEM SIDE PER 2002 NFPA 13R SEC. 6.6.5 AND NFPA 13 SEC. 7.1.1.
NO FDC IS NEEDED IF THE BUILDING IS LESS THAN 2000 SQUARE FEET PER 2002 NFPA 13R 6.6.4.1