Inspection History: FIRE SPKLR - FINAL

Permit Number - T09BU01478

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/25/2010 FIRE SPKLR - FINAL Approved HAD TO CHANGE OUT BAD FLOW SWITCH, TESTED AGAIN NO PROBLEMS.
10/21/2009 FIRE SPKLR - FINAL Not ready for Inspection NEED AS BUILTS, RISER DETAIL ON PLANS DIFFERENT THEN WHAT IS ON SITE. RISER SHALL HAVE 2 GAUGES ONE ON SUPPLY SIDE AND ONE ON SYSTEM SIDE PER 2002 NFPA 13R SEC. 6.6.5 AND NFPA 13 SEC. 7.1.1.
NO FDC IS NEEDED IF THE BUILDING IS LESS THAN 2000 SQUARE FEET PER 2002 NFPA 13R 6.6.4.1