Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T09BU01478
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2010 | FIRE SPKLR - FINAL | Approved | HAD TO CHANGE OUT BAD FLOW SWITCH, TESTED AGAIN NO PROBLEMS. | |
10/21/2009 | FIRE SPKLR - FINAL | Not ready for Inspection | NEED AS BUILTS, RISER DETAIL ON PLANS DIFFERENT THEN WHAT IS ON SITE. RISER SHALL HAVE 2 GAUGES ONE ON SUPPLY SIDE AND ONE ON SYSTEM SIDE PER 2002 NFPA 13R SEC. 6.6.5 AND NFPA 13 SEC. 7.1.1. NO FDC IS NEEDED IF THE BUILDING IS LESS THAN 2000 SQUARE FEET PER 2002 NFPA 13R 6.6.4.1 |