Permit: T09BU00927
Permit Details
Apply Date:
06/25/2009
Applicant:
UNITED FIRE EQUIPMENT CO,*C,*P
Description:
KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Contractors:
- UNITED FIRE EQUIPMENT CO,*C,*P
Permit Reviews
Permit Number - T09BU00927
Permit Status: Final
Permit Description: KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/08/2010 | MECHANICAL | 04/08/2010 | COMPLETED |
| 06/25/2009 | MECHANICAL | 06/25/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09BU00927
Permit Status: Final
Permit Description: KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/25/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T09BU00927
Permit Description: KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2009 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE M/C CABLE FROM INSIDE FILTER BANK 2) CONTINUE WALL FLASHING TO FLOOR 3) RAISE PIPING OFF OF FLOOR 4) PROVIDE MAKE-UP AIR 5) INTER LOCK MAKE UP AIR WITH EXHAUST FAN 6) SEAL HOLES IN HOOD EXTERIORS 7) REPAIR AND CAULK TRIM AND FLASHING ON HOOD AND BACK SPALSH PANELS TO PREVENT ANY SHARP OR OTHER WISE HAZARDOUS EDGES 8) PROVIDE GREASE RECEPTORS ON HOODS 9) PROVIDE ROOF JACKS FOR EXHAUST HOODS AND ELECTRIC CONDUIT 10) PROVIDE ENGINEERED DRAWINGS FOR HOOD EXHAUST SYSTEM 11) PROVIDE ACCESS TO GREASE DUCT CHASE OR WRAP 12) PROVIDE DISCONNECTS FOR EXHAUST FANS 13) PROVIDE APPROVED CONDUIT ON ROOF 14) THIS IS NOT A COMPLETE LIST |
| 06/26/2009 | FIRE - KITCHEN EXH HOOD FINAL | CSCHULTZ | Approved | |
| 05/25/2010 | PERMIT FINALED | GBONILLA | Approved |