Last Inspection Date Description Inspector Results Comments
08/27/2008 SIGN ELECTRIC N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/18/2008 SIGN SHOP N/A Partial Approval IVRS - Inspection :*
1. THIS SIGN IS NOT LISTED AS REQUIRED BY 600.3 NEC
2. NO MARKING ON SIGN AS REQUIRED BY 600.4 NEC
3. THE STRUCTURE OR FRAME WELDING DOES NOT APPEAR TO BE EFFECTIVE, WELD IS BUBBLED EXCESSIVELY AROUND AREAS TO BE JOINED
4. WIRING METHODS AS PER 600.5 AND 300 OK
5. IN LIEU OF LISTING SIGN, CONTR. REQUESTED A SIGN SHOP INSP. ADDRESS ITEMS #2, #3