Inspection History Details
Inspection Status: Partial Approval
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2008 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. THIS SIGN IS NOT LISTED AS REQUIRED BY 600.3 NEC 2. NO MARKING ON SIGN AS REQUIRED BY 600.4 NEC 3. THE STRUCTURE OR FRAME WELDING DOES NOT APPEAR TO BE EFFECTIVE, WELD IS BUBBLED EXCESSIVELY AROUND AREAS TO BE JOINED 4. WIRING METHODS AS PER 600.5 AND 300 OK 5. IN LIEU OF LISTING SIGN, CONTR. REQUESTED A SIGN SHOP INSP. ADDRESS ITEMS #2, #3 |
|
| 08/27/2008 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* A THIRD PARTY NRTL INSPECTION IS NEEDED SIGN SHOP IS NOT APPLICABLE AS PER DISCUSSIONS SEE SIGN INSPECTION |