Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
Permit Number - T08OT01595
Inspection Description - SIGN ELECTRIC
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/06/2008 | SIGN ELECTRIC | Partial Approval | NEED PAPERWORK | |
07/23/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT BOX, CONDUIT & SEAL TITE AS PER CODES 314.23, 348.30, 350.30 2. TIGHTEN LOOSE FITTINGS 3. A MARKING LABEL IS NEEDED - 600.4 4. SIGN TO BE LISTED AND LABELED - 600.3 5. NO PLANS OR PERMIT ON SITE |