Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address NEW:
333 E WETMORE RD #601
Apply Date:
10/16/2008
Applicant:
N/A
Description:
TI:OFFICE
Architects:
  • QUIHUIS, DANNY XAVIER
Contractors:
  • BARKER MORRISSEY CONTRACTING INC **C

Permit Reviews

Permit Number - T08CM03397
Permit Status: C of o
Permit Description: TI:OFFICE
Start Date Submittal Complete Date Status  
10/16/2008 PLANS OK TO SUBMIT - 3RD PARTY 10/20/2008 COMPLETED Review Details
10/20/2008 3RD PARTY REVIEW-COMMERCIAL TI 11/14/2008 COMPLETED Review Details
11/14/2008 POST 3RD PARTY REVIEW 11/17/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08CM03397
Permit Status: C of o
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date Name
10/16/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T08CM03397
Permit Description: TI:OFFICE
Total Completed Inspections - 28
Date Description Inspector Results Comments
11/26/2008 PLUMBING - PROGRESS RMYERS Approved
11/26/2008 PLUMBING - INTERMEDIATE RMYERS Approved
11/26/2008 PLUMBING - ROUGH, SOIL RMYERS Approved
12/09/2008 PLUMBING - ABOVE CEILING BBENEDON Approved IVRS - Inspection :*
WESTERN WATER TECH.
INJECTED 75PPM AT 6 LOCATIONS ON 12/8
SAMPLES TAKEN ON 12/9 WILL PROVIDE TEST REPORT
- LETTER RECEIVED FOR DELETION OF FD's IN RMS. 506, 606 AND 615 PER DANNY QUIHUIS (ARCHITECT)
12/09/2008 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
WEST HALF 5TH FLOOR
12/09/2008 FRAMING AQUIROZ Approved IVRS - Inspection :*
12/18/2008 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
5TH FLOOR
12/22/2008 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
COL. 7 NORTH TO 8 SOUTH TO WEST END
OF 5TH FLOOR OK FOR TILES MECH. ONLY
12/22/2008 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
1. SECURE VDV CABLING UPON EXITING OF CABLE TRAY
2. SUPPORT VDV CABLING AS PER 725.24, 800.24, 300.11, 725.3, 800.3

OK 2X4 LAY-INS 5 WEST 1/2
OK BORDERS ONLY 5 WEST 1/2
12/22/2008 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
12/22/2008 ELECTRIC - PROGRESS RHOLLAND Approved IVRS - Inspection :*
12/31/2008 MECHANICAL - PROGRESS MRAMBER Approved IVRS - Inspection :*
1) 5TH FLOOR OK FOR TILES
12/31/2008 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
5TH FLOOR:
1) DISCONNECTS TO A/C IN AN UNSAFE MOUNTING CONDITIONS
2) CLOSE OPENINGS TO BOXES WITH LIVE CIRCUITS
3) CAP UNUSED RELOC BLOCKS
4) CAP UNUSED CONDUITS
5) SUPPORT WIRES NEEDED FOR EXIT SIGNS
6) SUPPORT RELOCK WIRING PER APPLICABLE CODES
7) FINISH VDV CABELING
8) OK TO TILE EXCEPT AREAS NOTED
6TH FLOOR:
1) CHECK VDV CABELING THRU ACCESS OPENINGS
2) OK HARD LID LOBBY
12/31/2008 FIRE SPKLR - FINAL LTHOMAS Approved
01/20/2009 FIRE - FINAL LTHOMAS Approved
01/21/2009 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
01/26/2009 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
01/26/2009 NPPO - FINAL ACONNOR Approved N/A
01/26/2009 LANDSCAPE - FINAL ACONNOR Approved N/A
01/27/2009 RIGHT OF WAY - FINAL MOTERO Approved
01/29/2009 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
01/30/2009 BUILDING - PROGRESS AQUIROZ Approved IVRS - Inspection :*
02/04/2009 ELECTRIC - RECONNECT RHOLLAND Approved IVRS - Inspection :*
02/04/2009 ELECTRIC - CONSTRUCTION POWER RHOLLAND Approved IVRS - Inspection :*
02/04/2009 ENGINEERING - FINAL LHANLY Approved THIS INSPECTION WAS SCHEDULED 1-26-09 BUT NO RESULTS WERE ENTERED. NO WORK AT THIS SITE OCCURED ON THE EXTERIOR OF THE BUILDING. EXISTING CONDITIONS MAINTAINED.
02/04/2009 BUILDING - FINAL LHANLY Approved
02/05/2009 ELECTRIC - FINAL LHANLY Approved CONTRACTURAL WORK ON THIS PERMIT COMPLETE. NEC ARTICLE 240.33 ALLOWS FOR OTHER THAN VERTICAL MOUNTING OF DISCONNECTS WHEN IMPRACTIABLE. PER MANUFACTURER OF EQUIPMENT, AND AZ REGISTERED ENGINEER THE CIELING MOUNT OF THE G.E. "TH" DISCONNECTS IS SUITABLE.
02/09/2009 PERMIT FINALED LJACKSON Approved