Permit: T08CM03397

Parcel: 10510010D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM03397

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/04/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/21/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
6 WEST:
1. FINISH DISCONNECTS

OK TO TILE EXCEPT AS NOTED
01/16/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK LIGHT FIXTURES 6 WEST

1. SUPPORT OR REMOVE OLD CONDUITS LAYING ON GRID
2. SUPPORT MC AT 6' INTERVALS
3. LABEL DISCONNECTS
4. CLOSE OPEN BOXES
5. FINISH VDV CABLING
6. FINISH REMOUNTING A/C DISCONNECTS
01/09/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 6 EAST TO TILE EXCEPT AS NOTED
01/08/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
IS WHITE ENT LISTING AND PLENUM RATED
12/31/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
5TH FLOOR:
1) DISCONNECTS TO A/C IN AN UNSAFE MOUNTING CONDITIONS
2) CLOSE OPENINGS TO BOXES WITH LIVE CIRCUITS
3) CAP UNUSED RELOC BLOCKS
4) CAP UNUSED CONDUITS
5) SUPPORT WIRES NEEDED FOR EXIT SIGNS
6) SUPPORT RELOCK WIRING PER APPLICABLE CODES
7) FINISH VDV CABELING
8) OK TO TILE EXCEPT AREAS NOTED
6TH FLOOR:
1) CHECK VDV CABELING THRU ACCESS OPENINGS
2) OK HARD LID LOBBY
12/30/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
6TH FLOOR LOBBY:
1) SUPPORT M/C CABLE WITHIN 12" OF CANS
2) SUPPORT VDV CABLING 725.3 & 24, 800.3 & 24 AND 300.11
3) JUNCTION BOXES TO BE ACCESSIBLE
4) DISCONNECT TO A/C IN AN UNSAFE MOUNTING POSITION
12/23/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FINISH CABLE TRAY
2. WHITE & GRAY CABLES TO BE REMOVED OR SUPPORTED
12/22/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*