Permit: T08CM03397

Parcel: 10510010D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03397

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2009 ELECTRIC - FINAL Approved CONTRACTURAL WORK ON THIS PERMIT COMPLETE. NEC ARTICLE 240.33 ALLOWS FOR OTHER THAN VERTICAL MOUNTING OF DISCONNECTS WHEN IMPRACTIABLE. PER MANUFACTURER OF EQUIPMENT, AND AZ REGISTERED ENGINEER THE CIELING MOUNT OF THE G.E. "TH" DISCONNECTS IS SUITABLE.
02/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/30/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
6TH FLOOR ONLY:
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 ALSO, 314.21
2. FINISH OFFICE FURNITURE
3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 200.7
4. USE APPROVED HARDWARE FOR DEVICES
5. EM/EXIT LIGHTS TO BE AS ER 700.12(F)
6. DISCONNECTS PER 240.33
01/15/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ELECTRIC 2 POWER POLES
1. PROVIDE PHYSICAL PROTECTION
01/12/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. A DISCONNECTING MEANS IS NEEDED FOR INSTA-HOTS
2. PANEL DIRECTORIES TO BE AS PER 408.4
3. IDENTIFY CONDUCTOR PER AMENDMENT IN RELAY
BOXES 277V
4. FINISH A/C DISCONNECTS

EM LIGHTING IS OK - 5TH FLOOR