Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03397
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2009 | ELECTRIC - FINAL | Approved | CONTRACTURAL WORK ON THIS PERMIT COMPLETE. NEC ARTICLE 240.33 ALLOWS FOR OTHER THAN VERTICAL MOUNTING OF DISCONNECTS WHEN IMPRACTIABLE. PER MANUFACTURER OF EQUIPMENT, AND AZ REGISTERED ENGINEER THE CIELING MOUNT OF THE G.E. "TH" DISCONNECTS IS SUITABLE. | |
02/04/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
01/30/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 6TH FLOOR ONLY: 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 ALSO, 314.21 2. FINISH OFFICE FURNITURE 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 200.7 4. USE APPROVED HARDWARE FOR DEVICES 5. EM/EXIT LIGHTS TO BE AS ER 700.12(F) 6. DISCONNECTS PER 240.33 |
|
01/15/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ELECTRIC 2 POWER POLES 1. PROVIDE PHYSICAL PROTECTION |
|
01/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. A DISCONNECTING MEANS IS NEEDED FOR INSTA-HOTS 2. PANEL DIRECTORIES TO BE AS PER 408.4 3. IDENTIFY CONDUCTOR PER AMENDMENT IN RELAY BOXES 277V 4. FINISH A/C DISCONNECTS EM LIGHTING IS OK - 5TH FLOOR |