Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
3800 E RIVER RD
Apply Date:
07/22/2008
Applicant:
N/A
Description:
TI: WATER HEATER REPLACEMENT
Contractors:
  • RAGE ELECTRIC L L C
  • TUCSON PLUMBING SERVICE ,

Permit Reviews

Permit Number - T08CM02535
Permit Status: Expired
Permit Description: TI: WATER HEATER REPLACEMENT
Start Date Submittal Complete Date Status  
07/22/2008 COMMERCIAL TI 09/24/2008 COMPLETED Review Details
09/24/2008 COMMERCIAL TI 11/03/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08CM02535
Permit Status: Expired
Permit Description: TI: WATER HEATER REPLACEMENT
Total Outstanding Activity Conditions - 1
Date Name
07/22/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08CM02535
Permite Description: TI: WATER HEATER REPLACEMENT
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
BUILDING - FINAL N/A Not Inspected
10/21/2009 PLUMBING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PER INSTALLATION ILLUSTRATION, A CONDENSATE TRAP IS REQUIRED
2) T & P TERMINATION REQUIRES A MINIMUM 1" AIR GAP
3) WH'S ARE 199,000 BTU INSTALL EXPANSION TANKS AS SPECIFIED ON PLAN

Completed Inspections

Permit Status: Expired
Permit Number: T08CM02535
Permit Description: TI: WATER HEATER REPLACEMENT
Total Completed Inspections - 10
Date Description Inspector Results Comments
11/20/2008 PLUMBING - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
CHECKED GAS PIPING, WATER PIPING AND VENT PIPING
OK TO INSULATE WATER PIPING
11/20/2008 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROPERLY GROUND JUNCTION BOX -- NOT UNDER MOUNTING SCREW
2. FILL UNUSED OPENINGS -- NOT OLD FITTING
3. PLEASE VERIFY BOX FILL
4. NEED TO ADD ADDITIONAL ELECTRIC TO PLAN FOR
LOADS AND CIRCUITS
11/20/2008 FIRE - FINAL CSCHULTZ Approved
11/20/2008 ENGINEERING - FINAL JBRUCKME Approved
11/20/2008 SIGN - FINAL JYBARRA Approved
11/20/2008 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
11/21/2008 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
11/21/2008 NPPO - FINAL ACONNOR Approved N/A
11/21/2008 LANDSCAPE - FINAL ACONNOR Approved N/A
10/21/2009 PLUMBING - GAS PRESSURE TEST BBENEDON Approved IVRS - Inspection :*

Documents

File Name Document Type  
001__T1.TIF CONSTRPLANS VIEW
002__P1.TIF CONSTRPLANS VIEW
003__MP1.TIF CONSTRPLANS VIEW
004__E1.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW