Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* SAW LETTER FROM ENGINEER LOADS AND CIRCUITS OK GROUNDED PROPERLY BOX FILL OK |
|
| 11/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROPERLY GROUND JUNCTION BOX -- NOT UNDER MOUNTING SCREW 2. FILL UNUSED OPENINGS -- NOT OLD FITTING 3. PLEASE VERIFY BOX FILL 4. NEED TO ADD ADDITIONAL ELECTRIC TO PLAN FOR LOADS AND CIRCUITS |