Inspection History Details
Inspection Status: Cancelled
Inspection History: PLUMBING - FINAL
Permit Number - T08CM02535
Inspection Description - PLUMBING - FINAL
Inspection Status - Cancelled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2010 | PLUMBING - FINAL | Cancelled | CANCELLED PER DALE GREEN #349-4268 | |
03/17/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
10/21/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PER INSTALLATION ILLUSTRATION, A CONDENSATE TRAP IS REQUIRED 2) T & P TERMINATION REQUIRES A MINIMUM 1" AIR GAP 3) WH'S ARE 199,000 BTU INSTALL EXPANSION TANKS AS SPECIFIED ON PLAN |
|
03/04/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. YOU ARE REQUIRED TO POST YOUR ADDRESS! 2. REQUIRE 1 1/4" GAS TO EACH WATER HEATER 3. HEATERS ARE 300,000 BTU's AND REQUIRE ASME EXPANSION TANKS |