Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Address NEW:
6360 E GOLF LINKS RD
Apply Date:
06/04/2008
Applicant:
N/A
Description:
TI:SAFEWAY
Contractors:
  • HAUGEBAK CONSTRUCTION COMPANY ,

Permit Reviews

Permit Number - T08CM01902
Permit Status: Final
Permit Description: TI:SAFEWAY
Start Date Submittal Complete Date Status  
01/29/2009 REVISION - - 1ST 01/29/2009 COMPLETED Review Details
02/10/2009 REVISION - - 2ND 02/10/2009 COMPLETED Review Details
06/04/2008 PLANS OK TO SUBMIT - 3RD PARTY 06/04/2008 COMPLETED Review Details
06/04/2008 3RD PARTY REVIEW-COMMERCIAL TI 06/16/2008 COMPLETED Review Details
06/16/2008 POST 3RD PARTY REVIEW 07/07/2008 COMPLETED Review Details
12/18/2008 3RD PARTY REVIEW-REVISION/OTHER 01/20/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08CM01902
Permit Status: Final
Permit Description: TI:SAFEWAY
Total Outstanding Activity Conditions - 1
Date Name
06/04/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T08CM01902
Permit Description: TI:SAFEWAY
Total Completed Inspections - 24
Date Description Inspector Results Comments
07/10/2008 SHEET ROCK NAILING LHANLY Approved IVRS - Inspection :*
07/10/2008 FRAMING LHANLY Approved IVRS - Inspection :*
07/10/2008 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*
07/17/2008 RIGHT OF WAY - FINAL MCASTRO Approved
07/17/2008 PLUMBING - PRE SLAB RRICH Approved IVRS - Inspection :*
07/18/2008 NPPO - FINAL JLINVILL Approved
07/18/2008 LANDSCAPE - FINAL JLINVILL Approved
07/30/2008 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :*
DWV THRU ROOF FOR STARBUCKS PER REDLINE ON SITE OK
WILL REQUIRE CITY APPROVED PLAN SHOWING DIRECT DRAINAGES WITH AIR ADMITTANCE VALVES AT BOTH SINKS.
WATER PIPING UNDERGROUND AND IN WALL AT NORTH
WALL OK

AFTER HRS. INSP. CHK#6806257315 - $150.00
08/04/2008 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
08/04/2008 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
08/06/2008 ELECTRIC - UNDERGROUND RJIROUDE Approved IVRS - Inspection :*
08/12/2008 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
CONTRACTOR CANCELED
08/20/2008 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
THIS INSPECTION FOR MEAT/SEAFOOD PREP HAND SINK AND 2-COMP SINK FINAL OK
09/05/2008 ELECTRIC - ABOVE CEILING RJIROUDE Approved IVRS - Inspection :
See detailed listing on site.| 999*
09/05/2008 ELECTRIC - INTERMEDIATE RJIROUDE Approved IVRS - Inspection :*
09/05/2008 FIRE SPKLR - FINAL LTHOMAS Approved
09/05/2008 FIRE - FINAL LTHOMAS Approved
09/16/2008 ELECTRIC - FINAL RJIROUDE Approved IVRS - Inspection :*
1. NEED REVISED PLANS FOR CHANGE IN LIGHTING TO STORE
2. INSTALL END CAPS ON ROW LIGHTS
3. RECALL WHEN REVISION COMPLETE AND APPROVED
09/17/2008 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
SINK AT DELI SERVICE OK

1. NEED CALL IN AND APPROVAL OF ALL PLUMBING INSPECTIONS ON PERMIT CARD WITH RED LINE AND CITY APPROVED REVISION OF STARBUCKS PER NOTE 7/30/08
10/03/2008 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
EXISTING WATER HEATER IN BACK OF STORE HAS SERIOUS VENTING PROBLEMS. THE SMELL OF BURNT FUEL IS VERY STRONG AND MAY PRODUCE CARBON MONOXIDE INTO STORE.

WATER HEATER IS ALSO RUSTED & LEAKING WATER ONTO THE FLOOR. I RECOMMEND NOT USING THIS APPLIANCE UNTIL ALL ISSUES HAVE BEEN RESOLVED. PROVIDE A PERMIT IF REPLACING THE WATER HEATER.
02/02/2009 BUILDING ABOVE CEILING GDABBS Approved
02/02/2009 BUILDING - FINAL GDABBS Approved IVRS - Inspection :*
03/23/2009 ENGINEERING - FINAL MAVERY Approved
03/25/2009 SIGN - FINAL JYBARRA Approved