Permit: T08CM01902

Parcel: 136261260

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01902

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/21/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO ENERGIZE NEW 400 AMP. PANEL
CONNECT EQUIPMENT GROUND IN PANEL
2. NEED AIC RATING FOR PANEL R4
08/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK CEILING ABOVE MEAT CASE @ BUTCHER SHOP
2. SECURE BOXES AND CABLING @ BAKERY
08/15/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
08/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/04/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
07/29/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
FLORAL AREA CEILING
1. SEAL OPEN KNOCKOUT JUNCTION BOX
2. CLOSE OPEN JUNCTION

SEAFOOD FREEZER
1. FLEXIBLE METAL CONDUIT BROKEN WIRES HANGING OUT
07/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL LIGHT AND SERVICE RECEPTACLE FOR ICE MAKER CONDENSING UNITS
2. NEED TO INSTALL PROPER SIZE CONDUCTORS FOR ICE MAKER - SEE PLANS
3. NEED PROPER OVERCURRENT PROTECTION FOR ICE MAKER AND CONDENSING UNIT. PROVIDE INSTRUCTIONS
4. OK CEILING MEAT SALES AREA
CLOSE OPEN JUNCTION BOX
07/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*