Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
265 S CHURCH AV
Apply Date:
04/19/2007
Applicant:
EVAN PATTERSON
Description:
ELEC UPGRADES FOR MUSIC HALL AND TEMP CHILLERS ASSC W/T07CM00928
Contractors:
  • LEE MECHANICAL CONTRACTING INC ,

Permit Reviews

Permit Number - T07EL00698
Permit Status: Final
Permit Description: ELEC UPGRADES FOR MUSIC HALL AND TEMP CHILLERS ASSC W/T07CM00928
Start Date Submittal Complete Date Status  
04/19/2007 ELECTRICAL 04/19/2007 COMPLETED Review Details
04/19/2007 3RD PARTY REVIEW-REVISION/OTHER 04/26/2007 COMPLETED Review Details
05/02/2007 3RD PARTY REVIEW-REVISION/OTHER 05/02/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07EL00698
Permit Status: Final
Permit Description: ELEC UPGRADES FOR MUSIC HALL AND TEMP CHILLERS ASSC W/T07CM00928
Total Outstanding Activity Conditions - 1
Date Name
04/19/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T07EL00698
Permit Description: ELEC UPGRADES FOR MUSIC HALL AND TEMP CHILLERS ASSC W/T07CM00928
Total Completed Inspections - 7
Date Description Inspector Results Comments
05/14/2007 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
OK PRI-SEC CONDUITS AT LEO RICH CENTER
06/07/2007 ELECTRIC - TEMPORARY SERVICE DSANTACR Approved IVRS - Inspection :*
1) DO NOT ENERGIZE FEEDER TO CHILLERS UNTILL CLARIFICATION FOR USE OF SE TRIPLEX, SEE NOTES LAST INSPECTION
06/21/2007 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
1. PROVIDE TEST RESULTS FOR GFI TEST PRIOR TO ENERGIZING FEEDERS
2. RECEIVED LETTER FROM ENGINEER FOR APPROVAL OF SE CABLING
08/20/2007 ELECTRIC - RECONNECT DSANTACR Approved IVRS - Inspection :*
1) ORIGINAL INSPECTION NOTES: PROVIDE LETTER OF TORQUE FOR NEW 3000 AMP 208 GEAR
2) STILL NO RECORD OF GFI TEST PER NOTE #1 INSPECTION ON 6/2/107-1200 AMP 480V GEAR IS IN USE AT THIS TIME
3) CLEARANCE IS SUBJECT TO LETTER OF TORQUE FOR GEAR
-------------------------------------------------------------------------------------------------1) CONTRACTOR REQUESTED RETURN PM
2) INSPECTION UNSCHEDULED $108.00 PAID CHECK #10293
3) 3000 AMP 208 MUSIC HALL: DO NOT ENERGIZE NEW LOADS PRIOR TO INSPECTORS APPROVAL
4) INSULATING BUSHINGS POPED OFF AT J-BOX FOR FEEDERS INTO EXISTING GEAR, NEED MORE THREADS, INSULATING BUSHINGS CANNOT SEAT PROPERLY. GROUND GUTTER AT EXISTING GEAR
08/21/2007 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED FOR 265 S. CHURCH AVE PER D. SANTACRUZ
08/22/2007 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
RECEIVED LETTER FOR GFI MAIN TEST
02/18/2009 PERMIT FINALED BFLORES Approved