Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T07EL00698
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* 1) DO NOT ENERGIZE FEEDER TO CHILLERS UNTILL CLARIFICATION FOR USE OF SE TRIPLEX, SEE NOTES LAST INSPECTION |
|
06/06/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FEEDER CONDUCTORS TO BE IN APPROVED RACEWAYS SEE PLANS 2. VERIFY GROUNDING AT WEST SIDE OF BLD SERVICE AREA 3. SEE NOTES FROM PREVIOUS INSP. 6/4/07 |
|
06/04/2007 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1. PLEASE RECALL INSP. HAVE PLANS/PERMIT ON SITE LEAVE MESSAGE WITH INFO. OF INSP. REQUESTED LOCATION, ETC. 2. IF TEMP #3 IS THE CORRECT LOCATION, BOND ALL CONDUITS, NIPPLES AHEAD OF OVERCURRENT PER 250.94 NEC 3. CHASE NIPPLES NOT ALLOWED AT SERVICE TERMINATIONS. |