Inspection History Details
Permit: T07EL00698
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2009 | ELECTRIC - RECONNECT | Approved | ||
| 08/20/2007 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* 1) ORIGINAL INSPECTION NOTES: PROVIDE LETTER OF TORQUE FOR NEW 3000 AMP 208 GEAR 2) STILL NO RECORD OF GFI TEST PER NOTE #1 INSPECTION ON 6/2/107-1200 AMP 480V GEAR IS IN USE AT THIS TIME 3) CLEARANCE IS SUBJECT TO LETTER OF TORQUE FOR GEAR -------------------------------------------------------------------------------------------------1) CONTRACTOR REQUESTED RETURN PM 2) INSPECTION UNSCHEDULED $108.00 PAID CHECK #10293 3) 3000 AMP 208 MUSIC HALL: DO NOT ENERGIZE NEW LOADS PRIOR TO INSPECTORS APPROVAL 4) INSULATING BUSHINGS POPED OFF AT J-BOX FOR FEEDERS INTO EXISTING GEAR, NEED MORE THREADS, INSULATING BUSHINGS CANNOT SEAT PROPERLY. GROUND GUTTER AT EXISTING GEAR |