Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
7671 E TANQUE VERDE RD
Apply Date:
08/20/2007
Applicant:
CARRIER CORPORATION ,
Description:
CHILLER & COOLING TOWERS:REPLACE
Contractors:
  • CARRIER CORPORATION ,

Permit Reviews

Permit Number - T07CM03439
Permit Status: Final
Permit Description: CHILLER & COOLING TOWERS:REPLACE
Start Date Submittal Complete Date Status  
02/05/2008 REVISION - - 1ST 02/05/2008 ACTIVE Review Details
08/20/2007 OTHER 08/20/2007 COMPLETED Review Details
08/20/2007 OTHER 08/29/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM03439
Permit Status: Final
Permit Description: CHILLER & COOLING TOWERS:REPLACE
Total Outstanding Activity Conditions - 1
Date Name
08/20/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T07CM03439
Permit Description: CHILLER & COOLING TOWERS:REPLACE
Total Completed Inspections - 6
Date Description Inspector Results Comments
08/31/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
- INSTALL EXHAUST DUCT & DAMPER PER PLANS
- PROVIDE INTERLOCK FROM REFRIGERANT SENSOR TO BOILER AND WATER HEATERS.
- NEED TO TEST SENSORS
08/31/2007 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
08/31/2007 PLUMBING - FINAL BBENEDON Approved IVRS - Inspection :
See detailed listing on site.| 999*
BACKFLOW PROTECTION ON MAKE UP
08/31/2007 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/31/2007 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
1. ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM TERMINATIONS
2. BOND GUTTER ENCLOSURES - ALL
3. MAINTAIN WORKING CLEARANCE AT COOLING TOWER DISCONNECTS - ALL
4. FINISH ITEMS #1 & #4 OF PREVIOUS INSPECTIONS

* PLEASE VERIFY PERMIT FOR NEW BOILERS (2)
02/13/2008 PERMIT FINALED BFLORES Approved