Permit: T07CM03439
Permit Details
Status:
Final
Type:
COMMERCIAL OTHER
Address:
7671 E TANQUE VERDE RD
Address NEW:
7671 E TANQUE VERDE RD
Apply Date:
08/20/2007
Applicant:
CARRIER CORPORATION ,
Description:
CHILLER & COOLING TOWERS:REPLACE
Contractors:
- CARRIER CORPORATION ,
Permit Reviews
Permit Number - T07CM03439
Permit Status: Final
Permit Description: CHILLER & COOLING TOWERS:REPLACE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/05/2008 | REVISION - - 1ST | 02/05/2008 | ACTIVE |
| 08/20/2007 | OTHER | 08/20/2007 | COMPLETED |
| 08/20/2007 | OTHER | 08/29/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07CM03439
Permit Status: Final
Permit Description: CHILLER & COOLING TOWERS:REPLACE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/20/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07CM03439
Permit Description: CHILLER & COOLING TOWERS:REPLACE
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* - INSTALL EXHAUST DUCT & DAMPER PER PLANS - PROVIDE INTERLOCK FROM REFRIGERANT SENSOR TO BOILER AND WATER HEATERS. - NEED TO TEST SENSORS |
| 08/31/2007 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 08/31/2007 | PLUMBING - FINAL | BBENEDON | Approved | IVRS - Inspection : See detailed listing on site.| 999* BACKFLOW PROTECTION ON MAKE UP |
| 08/31/2007 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
| 12/31/2007 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* 1. ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM TERMINATIONS 2. BOND GUTTER ENCLOSURES - ALL 3. MAINTAIN WORKING CLEARANCE AT COOLING TOWER DISCONNECTS - ALL 4. FINISH ITEMS #1 & #4 OF PREVIOUS INSPECTIONS * PLEASE VERIFY PERMIT FOR NEW BOILERS (2) |
| 02/13/2008 | PERMIT FINALED | BFLORES | Approved |