Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03439
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS #3 & VERIFY PERMIT |
|
| 12/31/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM TERMINATIONS 2. BOND GUTTER ENCLOSURES - ALL 3. MAINTAIN WORKING CLEARANCE AT COOLING TOWER DISCONNECTS - ALL 4. FINISH ITEMS #1 & #4 OF PREVIOUS INSPECTIONS * PLEASE VERIFY PERMIT FOR NEW BOILERS (2) |
|
| 12/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* CALLED LEFT MESSAGE NO ONE ON SITE |
|
| 12/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED ETL TO VERIFY USAGE OF ALUMINUM WITH THIS LISTING |
|
| 12/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 08/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TIGHTEN LOOSE FITTINGS 2. SUPPORT PANEL A-1 IN WALL 3. TIGHTEN CONDUCTOR TERMINATIONS 4. ENTER SECTION SERVED WITH CIRCUITS 408.3(A)(3) 5. ANTI-OXIDE COMPOUND NEEDED FOR ALUMINUM CONDUCTORS 6. LISTING FOR EQUIPMENT STATES COPPER CONDUCTORS FOR GROUNDING PLANS ALSO 7. PLEASE HAVE ELECTRICAL ON SITE TO OPEN ALL EQUIPMENT |