Permit: T07CM03439

Parcel: 11446027E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03439

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH PREVIOUS ITEMS #3 & VERIFY PERMIT
12/31/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM TERMINATIONS
2. BOND GUTTER ENCLOSURES - ALL
3. MAINTAIN WORKING CLEARANCE AT COOLING TOWER DISCONNECTS - ALL
4. FINISH ITEMS #1 & #4 OF PREVIOUS INSPECTIONS

* PLEASE VERIFY PERMIT FOR NEW BOILERS (2)
12/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
CALLED LEFT MESSAGE NO ONE ON SITE
12/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED ETL TO VERIFY USAGE OF ALUMINUM WITH THIS LISTING
12/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
08/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TIGHTEN LOOSE FITTINGS
2. SUPPORT PANEL A-1 IN WALL
3. TIGHTEN CONDUCTOR TERMINATIONS
4. ENTER SECTION SERVED WITH CIRCUITS 408.3(A)(3)
5. ANTI-OXIDE COMPOUND NEEDED FOR ALUMINUM CONDUCTORS
6. LISTING FOR EQUIPMENT STATES COPPER CONDUCTORS FOR GROUNDING PLANS ALSO
7. PLEASE HAVE ELECTRICAL ON SITE TO OPEN ALL EQUIPMENT