Permit: T07CM03439

Parcel: 11446027E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM03439

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
TESTED REFRIGERANT SENSORS MECH. RM. 1
TESTED SENSORS & GAS SHUT OFF RM.2
02/07/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
MACHINERY ROOM 2 NEEDS AUTOMATIC SHUT OFF
IN GAS LINE TO BOILER & WATER HEATERS INTERLOCKED
WITH REFRIGERANT SENSORS
08/31/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- INSTALL EXHAUST DUCT & DAMPER PER PLANS
- PROVIDE INTERLOCK FROM REFRIGERANT SENSOR TO BOILER AND WATER HEATERS.
- NEED TO TEST SENSORS