Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM03439
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* TESTED REFRIGERANT SENSORS MECH. RM. 1 TESTED SENSORS & GAS SHUT OFF RM.2 |
|
| 02/07/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* MACHINERY ROOM 2 NEEDS AUTOMATIC SHUT OFF IN GAS LINE TO BOILER & WATER HEATERS INTERLOCKED WITH REFRIGERANT SENSORS |
|
| 08/31/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - INSTALL EXHAUST DUCT & DAMPER PER PLANS - PROVIDE INTERLOCK FROM REFRIGERANT SENSOR TO BOILER AND WATER HEATERS. - NEED TO TEST SENSORS |