Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
635 W VALENCIA RD
Apply Date:
04/04/2007
Applicant:
C P R ELECTRIC
Description:
NEW COOLER:FREEZER
Contractors:
  • C P R ELECTRIC

Permit Reviews

Permit Number - T07CM01405
Permit Status: Expired
Permit Description: NEW COOLER:FREEZER
Start Date Submittal Complete Date Status  
04/04/2007 COMMERCIAL TI 05/01/2007 COMPLETED Review Details
05/01/2007 COMMERCIAL TI 06/06/2007 COMPLETED Review Details
06/06/2007 RESUBMITTAL 06/18/2007 COMPLETED Review Details
06/18/2007 RESUBMITTAL 06/25/2007 COMPLETED Review Details
06/25/2007 RESUBMITTAL 07/19/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM01405
Permit Status: Expired
Permit Description: NEW COOLER:FREEZER
Total Outstanding Activity Conditions - 1
Date Name
04/04/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07CM01405
Permite Description: NEW COOLER:FREEZER
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
07/24/2007 BUILDING - FINAL N/A Partial Approval IVRS - Inspection :*
FINAL INSPECTION SHALL BE MADE AFTER ALL WORK REQUIRED BY BUILDING PERMIT IS COMPLETED IN ACCORDANCE WITH THE SECTION 109.3.10 IBC

THIS PARTIAL INSPECTION COVERS INSTALLATION OF PRE-FAB FREEZER UNITS ONLY, TO OBTAIN BUILDING FINAL ALSO, NEED TO PROVIDE INSTALLATION OF FREEZER AND COOLER ON/IN STOCKROOM OR DELETE BY NEW REVISION WITH DSD CITY OF TUCSON PLANS EXAMINER
07/24/2007 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTR. NOT ON SITE
PLEASE SEE LOCKS, HOLDS, BE SURE TO ADDRESS PRIOR TO CALLING INSPECTION
07/24/2007 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection :*
PROVIDE DISCONNECTS WITH OVERCURRENT PROTECTION FOR WALK IN CONDENSORS
07/24/2007 FIRE SPKLR - FINAL N/A Denied Need to install sprinklers in the freezer and cooler. Need approved plans and permits before work is done.
Need an up to date sprinkler inspection, last inspection on file is 12/05/03. Inspections need to be done yearly.
Need a 5-year alarm check valve inspection done, a separate report is needed for this or this inspection must be shown on the sprinkler report.
Need to label the fire riser room door "FIRE RISER".
Need to install a fire department key box for riser room.
07/24/2007 FIRE - FINAL N/A Denied Need to install sprinklers in the freezer and cooler. Need approved plans and permits before work is done.
Need an up to date sprinkler inspection, last inspection on file is 12/05/03. Inspections need to be done yearly.
Need a 5-year alarm check valve inspection done, a separate report is needed for this or this inspection must be shown on the sprinkler report.
Need to label the fire riser room door "FIRE RISER".
Need to install a fire department key box for riser room.

Documents

File Name Document Type  
None DOCUMENTS VIEW
T07CM01405_001.TIF CONSTRPLANS VIEW
T07CM01405_002.TIF CONSTRPLANS VIEW
T07CM01405_003.TIF CONSTRPLANS VIEW
T07CM01405_004.TIF CONSTRPLANS VIEW
T07CM01405_005.TIF CONSTRPLANS VIEW