Inspection History Details
Inspection Status: Denied
Inspection History: FIRE SPKLR - FINAL
Permit Number - T07CM01405
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2007 | FIRE SPKLR - FINAL | Denied | Need to install sprinklers in the freezer and cooler. Need approved plans and permits before work is done. Need an up to date sprinkler inspection, last inspection on file is 12/05/03. Inspections need to be done yearly. Need a 5-year alarm check valve inspection done, a separate report is needed for this or this inspection must be shown on the sprinkler report. Need to label the fire riser room door "FIRE RISER". Need to install a fire department key box for riser room. |