Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM01405

Parcel: 13804180C


Addresses:

635 W VALENCIA RD


Inspection Status: Denied

Inspection History: FIRE SPKLR - FINAL

Permit Number - T07CM01405

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
07/24/2007 FIRE SPKLR - FINAL Denied Need to install sprinklers in the freezer and cooler. Need approved plans and permits before work is done.
Need an up to date sprinkler inspection, last inspection on file is 12/05/03. Inspections need to be done yearly.
Need a 5-year alarm check valve inspection done, a separate report is needed for this or this inspection must be shown on the sprinkler report.
Need to label the fire riser room door "FIRE RISER".
Need to install a fire department key box for riser room.