Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01405
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/10/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Architect shall sign and date seals on all sheets, both sets. |
| 04/19/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide manufacturer's listing and equipment data along with mechanical and electrical operating information for the new freezer/cooler units. Reference Section 301.6, IMC 2003. |
| 04/19/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/19/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/19/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/01/2007 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
| 05/01/2007 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 05/01/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/01/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 05/01/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 05/01/2007 | DELMA ROBEY | REJECT SHELF | Completed |