Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
4444 E GRANT RD
Address NEW:
4444 E GRANT RD
Apply Date:
09/26/2007
Applicant:
R C I SYSTEMS INC
Description:
KITCHEN HOOD SYSTEM
Contractors:
  • R C I SYSTEMS INC

Permit Reviews

Permit Number - T07BU02040
Permit Status: Expired
Permit Description: KITCHEN HOOD SYSTEM
Start Date Submittal Complete Date Status  
09/26/2007 MECHANICAL 09/26/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07BU02040
Permit Status: Expired
Permit Description: KITCHEN HOOD SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
09/26/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07BU02040
Permite Description: KITCHEN HOOD SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
12/14/2007 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection :*
- EXHAUST HOOD & EXHAUST DUCT ARE OK FOR TYPE I REQUIREMENTS
- 2 OF THE FITTERS ARE HOMEMADE & NEED TO BE LISTED, APPROVED FILTERS LIKE THE OTHER 2
- THE MAKE UP AIR UNIT DOES NOT WORK
- YOU CANNOT USE EXTENSION CORDS TO POWER THE APPLIANCES PLUGGED INTO AN UNAPPROVED RECEPTACLE
- HAVE A QUALIFIED ELECTRICIAN INTERLOCK THE MAKE UP AIR WITH THE EXHAUST FAN & FIX ALL WIRING ISSUES
- THE EXHAUST FAN IS NOT COMPLETE
- SOME PIECES ARE LAYING ON THE ROOF & OTHERS ARE NOT PROPERLY ATTACHED TO FAN HOUSING.
12/14/2007 FIRE - KITCHEN EXH HOOD FINAL N/A Not ready for Inspection MECH. NOT FINALED YET.