Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T07BU02040
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EXHAUST FAN ON ROOF IS BROKEN & UNREPAIRABLE AND DOES NOT FIT PROPERLY ON EXISTING CURB. TOP OF FAN DISCHARGE MUST BE MIN. 40" ABOVE ROOF. PROVIDE A DISCONNECT FOR EXHAUST FAN. EXTENSION CORD INSIDE CONDUIT IS NOT AN APPROVED METHOD. CONDUITS MUST BE SUPPORTED. PROVIDE A PERMIT. |
|
12/14/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - EXHAUST HOOD & EXHAUST DUCT ARE OK FOR TYPE I REQUIREMENTS - 2 OF THE FITTERS ARE HOMEMADE & NEED TO BE LISTED, APPROVED FILTERS LIKE THE OTHER 2 - THE MAKE UP AIR UNIT DOES NOT WORK - YOU CANNOT USE EXTENSION CORDS TO POWER THE APPLIANCES PLUGGED INTO AN UNAPPROVED RECEPTACLE - HAVE A QUALIFIED ELECTRICIAN INTERLOCK THE MAKE UP AIR WITH THE EXHAUST FAN & FIX ALL WIRING ISSUES - THE EXHAUST FAN IS NOT COMPLETE - SOME PIECES ARE LAYING ON THE ROOF & OTHERS ARE NOT PROPERLY ATTACHED TO FAN HOUSING. |