Permit: T07BU02040

Parcel: 12205003C


Addresses:

4444 E GRANT RD

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/17/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EXHAUST FAN ON ROOF IS BROKEN & UNREPAIRABLE AND DOES NOT FIT PROPERLY ON EXISTING CURB. TOP OF FAN DISCHARGE MUST BE MIN. 40" ABOVE ROOF. PROVIDE A DISCONNECT FOR EXHAUST FAN. EXTENSION CORD INSIDE CONDUIT IS NOT AN APPROVED METHOD. CONDUITS MUST BE SUPPORTED. PROVIDE A PERMIT.
12/14/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- EXHAUST HOOD & EXHAUST DUCT ARE OK FOR TYPE I REQUIREMENTS
- 2 OF THE FITTERS ARE HOMEMADE & NEED TO BE LISTED, APPROVED FILTERS LIKE THE OTHER 2
- THE MAKE UP AIR UNIT DOES NOT WORK
- YOU CANNOT USE EXTENSION CORDS TO POWER THE APPLIANCES PLUGGED INTO AN UNAPPROVED RECEPTACLE
- HAVE A QUALIFIED ELECTRICIAN INTERLOCK THE MAKE UP AIR WITH THE EXHAUST FAN & FIX ALL WIRING ISSUES
- THE EXHAUST FAN IS NOT COMPLETE
- SOME PIECES ARE LAYING ON THE ROOF & OTHERS ARE NOT PROPERLY ATTACHED TO FAN HOUSING.