Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
07/02/2007
Applicant:
INDEPENDENT FIRE AND SAFETY L L C
Description:
KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Contractors:
  • INDEPENDENT FIRE AND SAFETY L L C

Permit Reviews

Permit Number - T07BU01439
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Start Date Submittal Complete Date Status  
07/02/2007 MECHANICAL 07/03/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07BU01439
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
07/02/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07BU01439
Permite Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
03/09/2009 FIRE - KITCHEN EXH HOOD FINAL N/A Denied 1. CENTER NOZZLES (ADP) IN DUCT PER INSTALLATION REQUIRMENTS.
2. OVER GIDDLE LOWER ADP NOZZLE WITHIN RANGE REQUIREMNTS
3. AS BUILTS NEEDED
4. MOVE PULL STATION 10 FEET AWAY FROM DEEP FYERS

Completed Inspections

Permit Status: Expired
Permit Number: T07BU01439
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Completed Inspections - 1
Date Description Inspector Results Comments
07/24/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :
See detailed listing on site.| 999*
1. THE HOOD MEETS TYPE 1 REQUIREMENTS
HOWEVER, THE DUCT SHAFT DOES NOT MEET CODE.
IT NEEDS TO BE EXTENDED DOWN TO WHERE THE GREASE DUCT PENETRATES THE CEILING.
2. MAKE UP AIR NOT INTERLOCKED WITH EXHAUST FAN
3. EXHAUST FAN IS TYPE I
AN EXTENSION CORD CANNOT BE USED TO POWER THE EXHAUST FAN.
4. REMOVE ANY GAS PIPING, CONDUITS, ETC FROM INSIDE SHAFT.

Documents

File Name Document Type  
None DOCUMENTS VIEW
HOOD_01.TIF FIRE PLANS VIEW