Permit: T07BU01439
Permit Details
Apply Date:
07/02/2007
Applicant:
INDEPENDENT FIRE AND SAFETY L L C
Description:
KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Contractors:
- INDEPENDENT FIRE AND SAFETY L L C
Permit Reviews
Permit Number - T07BU01439
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
07/02/2007 | MECHANICAL | 07/03/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07BU01439
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/02/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07BU01439
Permite Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2009 | FIRE - KITCHEN EXH HOOD FINAL | N/A | Denied | 1. CENTER NOZZLES (ADP) IN DUCT PER INSTALLATION REQUIRMENTS. 2. OVER GIDDLE LOWER ADP NOZZLE WITHIN RANGE REQUIREMNTS 3. AS BUILTS NEEDED 4. MOVE PULL STATION 10 FEET AWAY FROM DEEP FYERS |
Completed Inspections
Permit Status: Expired
Permit Number: T07BU01439
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. THE HOOD MEETS TYPE 1 REQUIREMENTS HOWEVER, THE DUCT SHAFT DOES NOT MEET CODE. IT NEEDS TO BE EXTENDED DOWN TO WHERE THE GREASE DUCT PENETRATES THE CEILING. 2. MAKE UP AIR NOT INTERLOCKED WITH EXHAUST FAN 3. EXHAUST FAN IS TYPE I AN EXTENSION CORD CANNOT BE USED TO POWER THE EXHAUST FAN. 4. REMOVE ANY GAS PIPING, CONDUITS, ETC FROM INSIDE SHAFT. |