Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07BU01439
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
07/24/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE HOOD MEETS TYPE 1 REQUIREMENTS HOWEVER, THE DUCT SHAFT DOES NOT MEET CODE. IT NEEDS TO BE EXTENDED DOWN TO WHERE THE GREASE DUCT PENETRATES THE CEILING. 2. MAKE UP AIR NOT INTERLOCKED WITH EXHAUST FAN 3. EXHAUST FAN IS TYPE I AN EXTENSION CORD CANNOT BE USED TO POWER THE EXHAUST FAN. 4. REMOVE ANY GAS PIPING, CONDUITS, ETC FROM INSIDE SHAFT. |
|
07/12/2007 | MECHANICAL - FINAL | Denied | THERE IS NO SUITE NUMBER POSTED ON THE PERMIT AND NO CONTACT PHONE NUMBERS. COULD NOT DO INSPECTION |