Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T07BU01439

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
03/09/2009 FIRE - KITCHEN EXH HOOD FINAL Denied 1. CENTER NOZZLES (ADP) IN DUCT PER INSTALLATION REQUIRMENTS.
2. OVER GIDDLE LOWER ADP NOZZLE WITHIN RANGE REQUIREMNTS
3. AS BUILTS NEEDED
4. MOVE PULL STATION 10 FEET AWAY FROM DEEP FYERS