Permit: T07BU00189
Permit Details
Apply Date:
01/25/2007
Applicant:
ROADRUNNER FIRE* C
Description:
KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Contractors:
- ROADRUNNER FIRE* C
Permit Reviews
Permit Number - T07BU00189
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/25/2007 | MECHANICAL | 01/25/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07BU00189
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
01/25/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07BU00189
Permite Description: KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2007 | FIRE - KITCHEN EXH HOOD FINAL | N/A | Denied | 1.) Lower nozzles on griddles need 10" to 20" height 2.) Reposition nozzles or move range on south end. Aim point is center of range. 3.) Clean hood and cooking equipment to bare metal. 4.) Repair or replace outlet under fryer on north end. 5.) Need to have mechanical final called in 04090. |
12/04/2007 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* PROVIDE INTERLOCK AT EXHAUST/M.U.A ALL OTHER CORRECTIONS MADE |