Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2007 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1.) Lower nozzles on griddles need 10" to 20" height 2.) Reposition nozzles or move range on south end. Aim point is center of range. 3.) Clean hood and cooking equipment to bare metal. 4.) Repair or replace outlet under fryer on north end. 5.) Need to have mechanical final called in 04090. |