Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
09/21/2007 FIRE - KITCHEN EXH HOOD FINAL Denied 1.) Lower nozzles on griddles need 10" to 20" height
2.) Reposition nozzles or move range on south end. Aim point is center of range.
3.) Clean hood and cooking equipment to bare metal.
4.) Repair or replace outlet under fryer on north end.
5.) Need to have mechanical final called in 04090.