Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T07BU00189
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE ON SITE |
|
12/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE INTERLOCK AT EXHAUST/M.U.A ALL OTHER CORRECTIONS MADE |
|
11/09/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/24/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - INTERLOCK MAKE UP AIR WITH EXHAUST SYSTEM - PROVIDE DOCUMENTATION ON FLEX CONNECTOR AT EXHAUST FAN, SUITABLE FOR GREASE DUCT APPLICATION - PROVIDE GREASE TROFT ON ROOF UNDER EXHAUST FAN DISCHARGE - PROVIDE DOCUMENT FROM FIRE MARSHALL THAT SHUNT SYSTEM WORKING PROPERLY |