Permit: T06PL01720
Permit Details
Apply Date:
09/26/2006
Applicant:
BENDEL DONALD
Description:
GAS LINE:REPLACE R1 Add water heater
Permit Reviews
Permit Number - T06PL01720
Permit Status: Expired
Permit Description: GAS LINE:REPLACE R1 Add water heater
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/26/2006 | PLUMBING | 09/26/2006 | COMPLETED |
| 10/13/2006 | PLUMBING | 10/13/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06PL01720
Permit Status: Expired
Permit Description: GAS LINE:REPLACE R1 Add water heater
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/26/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06PL01720
Permite Description: GAS LINE:REPLACE R1 Add water heater
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2006 | PLUMBING - FINAL | N/A | Partial Approval | IVRS - Inspection :* - PIPING IS OK - READ INSPECTION NOTES! - SECURE ALL JOINTS ON VENT CONNECTOR W/SHEETMETAL SCREWS - PROVIDE 1" MINIMUM CLEARANCE FROM WOOD. - TYPE B VENT SHALL TERMINATE ONE FOOT MINIMUM ABOVE ROOF. - OK FOR GAS AFTER CORRECTING. |
Completed Inspections
Permit Status: Expired
Permit Number: T06PL01720
Permit Description: GAS LINE:REPLACE R1 Add water heater
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2006 | PLUMBING - GAS PRESSURE TEST | BBENEDON | Approved | IVRS - Inspection :* |