Permit: T06PL01720

Parcel: 121070500


Addresses:

1302 N SONOITA AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/18/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10/17/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE DOUBLE WALL B VENT FROM 6" BELOW WOOD CEILING AND EXTERIOR THROUGH ROOF TO TERMINATION
2. 3/4 PIPE SECTION SERVING 180,000 BTU IS UNDERSIZED 1" PIPE REQUIRED TO FIRST BRANCH CONNECTION.
10/12/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*