Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - PIPING IS OK - READ INSPECTION NOTES! - SECURE ALL JOINTS ON VENT CONNECTOR W/SHEETMETAL SCREWS - PROVIDE 1" MINIMUM CLEARANCE FROM WOOD. - TYPE B VENT SHALL TERMINATE ONE FOOT MINIMUM ABOVE ROOF. - OK FOR GAS AFTER CORRECTING. |
|
| 10/17/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/12/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PIPE SUPPORTS SHALL BE WEATHER RESISTANT. REDWOOD IS OK - FLASHING REQUIRED AT ROOF PENETRATION AT EVE - ADD NEW WATER HEATER TO PERMIT. - PIPE 1" THROUGH FIRST TEE. TEE SHALL BE FULL SIZE. - SEDIMENT TRAPS REQUIRED AT WH AND FURNACE. - BOND GAS PIPE. GROUND TO WATER. - WH VENT CONNECTOR SHALL BE GALVANIZED. - SECURE W/SCREWS. - TYPE B VENT REQUIRED THROUGH ROOF, PROVIDE 1" CLEAR - T&P SHALL NOT BE TRAPPED BUT SHALL GRAVITY DRAIN. - BLACK IRON NIPPLES NOT ACCEPTABLE AT T&P AND WATER SUPPLY INLET & OUTLET - PRESSURE GAUGE SHALL HAVE 1/10 PSI INCREMENTATION. (15 PSI) |