Permit: T06OT01164
Permit Details
Apply Date:
05/02/2006
Applicant:
MEDOFF DONALD
Description:
C OF O: USED CAR LOT
Permit Reviews
Permit Number - T06OT01164
Permit Status: C of o
Permit Description: C OF O: USED CAR LOT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/02/2006 | C OF O | 05/04/2006 | COMPLETED |
Completed Inspections
Permit Status: C of o
Permit Number: T06OT01164
Permit Description: C OF O: USED CAR LOT
Total Completed Inspections - 8
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2006 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 08/31/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
| 08/31/2006 | FIRE - FINAL | LLAKEY | Approved | |
| 09/06/2006 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* |
| 09/12/2006 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 09/12/2006 | ELECTRIC - FINAL | RHOLLAND | Approved | 1. NEED BONDING DEVICE IN CT CAN -- 250.92 2. BOND ENCLOSURES 3. PREVENT OBJECTIONABLE CURRENT -- 250.6 4. NEED REJECTION PINS 5. GAS BOND TO INTERIOR SIDE PIPING 6. ADD SERVICE UPGRADE TO PERMIT -- WORK IS BEYOND C OF O |
| 09/13/2006 | CERTIFICATE OF OCCUPANCY | LHANLY | Approved | IVRS - Inspection :* |
| 09/14/2006 | PERMIT FINALED | DROBEY | Approved |