Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2006 | ELECTRIC - FINAL | Partial Approval | 1. NEED BONDING DEVICE IN CT CAN -- 250.92 2. BOND ENCLOSURES 3. PREVENT OBJECTIONABLE CURRENT -- 250.6 4. NEED REJECTION PINS 5. GAS BOND TO INTERIOR SIDE PIPING 6. ADD SERVICE UPGRADE TO PERMIT -- WORK IS BEYOND C OF O |
|
| 09/12/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/23/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MISSING COVER PLATES. 2. FILL UNUSED OPENING IN PANEL. 3. WE HAVE EXPOSED CONDUCTORS ABOVE CEILING. 4. PROPERLY SUPPORT NM CABLE ABOVE CEILING ALSO LIGHT FIXTURES. 5. WATER HEATER NOT TO BE CORD & PLUG CONNECTED. 6. RE-ATTACH LIGHT FIXTURE TO CEILING. 7. USE AN APPROVED GROUND BAR WITH PANEL. 8. GROUNDED CONDUCTORS TO BE IDENTIFIED ENTIRE LENGTH. 9. SECURE CABLE TO ENCLOSURE. 10. HAVE A LICENSED L-11 CONTRACTOR PERFORM WORK. |
|
| 05/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LABEL ALL DISCONNECTING MEANS AND METER WITH ADDRESS. 2. CLEAN AND RE-TORQUE TERMINATION AT SERVICE. 3. FREE UP TO OPEN ALL DISCONNECTS. 4. BROKEN PHOTO SENSOR. 5. REPLACE MISSING COVER PLATES. 6. LIGHTING TO MEET OUTDOOR LIGHTING CODES. 7. SUPPORT CONDUITS AS PER CODE. 8. WE HAVE EXPOSED CONDUCTORS. 9. LOCKED NEED ACCESS TO INTERIOR. |