Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06EL00408
Permit Details
Status:
Expired
Type:
COMMERCIAL OTHER
Address:
811 E WETMORE RD 03
Address NEW:
811 E WETMORE RD 03
Apply Date:
03/01/2006
Applicant:
FINA COMPANIES L L C
Description:
ELECTRIC SERVICE REPAIR
Contractors:
- FINA COMPANIES L L C
Outstanding Activity Conditions
Permit Number - T06EL00408
Permit Status: Expired
Permit Description: ELECTRIC SERVICE REPAIR
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/01/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL00408
Permite Description: ELECTRIC SERVICE REPAIR
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2006 | ELECTRIC - INTERMEDIATE | N/A | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE LETTER OF APPROVAL FROM ENG OR SQ D TECH ON SERVICE RE-ENERGIZING 2. PROVIDE LETTER OR APPROVAL FROM ENG OF RECORD ON PLANS ON APPROVAL IN ISOLATION OF 1 RUN OF 4-500MCM CONDUCTOR SET AND USE OR ONLY 2 SETS TO PROVIDE POWER FOR EXISTING SITUATION. 3. PROVIDE INFO ON SETTING OF 1200A CB IF ADJUSTABLE TO WHAT AMPERAGES RECALL FOR RECONNECT. |
| 03/02/2006 | ELECTRIC - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* RECEIVED LETTER FROM SY REP ON APPROVAL OF EQUIPMENT (SERVICE) TO REENERGIZE. FOUR SPLICE BUS BARS IN BUS PANEL BETWEEN DISCONNECT INCLUDING BUS BRACKET REPLACED 0- VOLTAGE ON ENCLOSURE DAMAGED C PHASE 500 MCM UPPER REPLACED - 190' LENGTH BY M & B MECH & ELECT MIKE LOFTIS GROUND WIRE COPPER TO GEAR 0.3 S/0.4S/S.4/ CHECK PER FINA TO BE TAKEN TO CITY OFFICE FRI AM |
Completed Inspections
Permit Status: Expired
Permit Number: T06EL00408
Permit Description: ELECTRIC SERVICE REPAIR
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2006 | TEP CLEARANCE - AM | JKOZUCH | Approved | ECO |