Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE LETTER OF APPROVAL FROM ENG OR SQ D TECH ON SERVICE RE-ENERGIZING 2. PROVIDE LETTER OR APPROVAL FROM ENG OF RECORD ON PLANS ON APPROVAL IN ISOLATION OF 1 RUN OF 4-500MCM CONDUCTOR SET AND USE OR ONLY 2 SETS TO PROVIDE POWER FOR EXISTING SITUATION. 3. PROVIDE INFO ON SETTING OF 1200A CB IF ADJUSTABLE TO WHAT AMPERAGES RECALL FOR RECONNECT. |