Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL00408
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* RECEIVED LETTER FROM SY REP ON APPROVAL OF EQUIPMENT (SERVICE) TO REENERGIZE. FOUR SPLICE BUS BARS IN BUS PANEL BETWEEN DISCONNECT INCLUDING BUS BRACKET REPLACED 0- VOLTAGE ON ENCLOSURE DAMAGED C PHASE 500 MCM UPPER REPLACED - 190' LENGTH BY M & B MECH & ELECT MIKE LOFTIS GROUND WIRE COPPER TO GEAR 0.3 S/0.4S/S.4/ CHECK PER FINA TO BE TAKEN TO CITY OFFICE FRI AM |