Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Apply Date:
09/08/2006
Applicant:
N/A
Description:
Senita Valley ELEMENTARY SCHOOL - PRESCHOOL
Architects:
  • ORCUTT, HERMAN LAWRENCE
Contractors:
  • DIVERSIFIED DESIGN AND CONSTRUCT

Permit Reviews

Permit Number - T06CM04951
Permit Status: C of o
Permit Description: Senita Valley ELEMENTARY SCHOOL - PRESCHOOL
Start Date Submittal Complete Date Status  
02/12/2008 POST 3RD PARTY REVIEW 02/19/2008 COMPLETED Review Details
03/26/2007 POST 3RD PARTY REVIEW 05/23/2007 COMPLETED Review Details
03/26/2007 SITE 06/06/2007 COMPLETED Review Details
05/23/2007 RESUBMITTAL 06/11/2007 COMPLETED Review Details
07/09/2007 REVISION - - 1ST 07/09/2007 COMPLETED Review Details
09/08/2006 PLANS OK TO SUBMIT - 3RD PARTY 09/27/2006 COMPLETED Review Details
09/08/2006 PLANS OK TO SUBMIT - SITE 09/13/2006 COMPLETED Review Details
09/10/2007 POST 3RD PARTY REVIEW 09/28/2007 COMPLETED Review Details
09/27/2006 3RD PARTY REVIEW-COMMERCIAL 03/26/2007 COMPLETED Review Details
10/02/2006 SITE 03/22/2007 COMPLETED Review Details
11/19/2007 3RD PARTY REVIEW-REVISION/OTHER 11/19/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM04951
Permit Status: C of o
Permit Description: Senita Valley ELEMENTARY SCHOOL - PRESCHOOL
Total Outstanding Activity Conditions - 1
Date Name
09/08/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T06CM04951
Permit Description: Senita Valley ELEMENTARY SCHOOL - PRESCHOOL
Total Completed Inspections - 44
Date Description Inspector Results Comments
06/21/2007 EXCAVATION/LAYOUT REBAR & ZON GDABBS Approved IVRS - Inspection :*
1. INTERIOR TOE DOWN FOOTING FOR BEARING WALL - BLDG A
2. END WALL TOE DOWN FOOTINGS BLD. A - OK TO POUR
07/11/2007 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :*
8" SDR 35 FROM EXISTING MANHOLE #2 300' SOUTH
BEDDING, LAYING, TRACER, SHADING OK
07/31/2007 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*
REST OF "A" OK -- FINISH WRAPPING PLUMBING
08/02/2007 PLUMBING - PRE SLAB RRICH Approved IVRS - Inspection :*
8" SDR PIPING TO MANHOLE #2,
8" SDR CONTINUES SOUTH APP. 20' SOUTH OF MANHOLE #2, #2 BASE POURED OK TO STACK

BUILDING A PRE-SLAB OK
08/22/2007 REINFORCED MASONRY PRE-GROUT GDABBS Approved IVRS - Inspection :*
LAST CMU WALL @ B1/4.2 -- OK TO GROUT TOP OUT
08/22/2007 ELECTRIC - UNDERGROUND RJIROUDE Approved IVRS - Inspection :*
09/20/2007 ROOF NAILING GDABBS Approved IVRS - Inspection :*
10/04/2007 ELECTRIC - INTERMEDIATE RJIROUDE Approved IVRS - Inspection :*
1) OK WALLS BLDG A
10/08/2007 PLUMBING - GAS PRESSURE TEST RRICH Approved IVRS - Inspection :*
FROM METER TO (5 ROOFTOP UNITS IN PRE-SCHOOL TEST OK
10/12/2007 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
CHECKED CONDENSATE DRAINS BLDG. A
OK TO INSULATE & COVER WALLS
10/15/2007 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
WATER TEST DWV THRU ROOF OK
AIR TEST WATER PIPING OK FROM STUBOUT OF BUILDING

1. SHALL SEE CLOSET FLANGE INSTALL PRIOR TO SETTING STOOLS
11/13/2007 SHEET ROCK NAILING GDABBS Approved IVRS - Inspection :*
1) RESTROOMS
11/16/2007 ELECTRIC - ABOVE CEILING RJIROUDE Approved IVRS - Inspection :*
OK HARD LIDS RMS 001, 002, 003, 004 B
104, 114, 117, 121, 125, 124, 112
12/03/2007 STUCCO MESH GDABBS Approved IVRS - Inspection :*
12/28/2007 SITE - SEWER RRICH Approved IVRS - Inspection :*
FROM MANHOLE #7, 6" SDR 35 TO END OF LINE OK
PENDING VERIFICATION OF GRADE & AIR TESTING
02/29/2008 PLUMBING - YARD WTR LINE/TEST RRICH Approved IVRS - Inspection :*
03/05/2008 TEP CLEARANCE - PM JWEATHER Approved TEC CLEARED FOR BLDGS 1 THRU 4 PER R. JIROUDEK
03/19/2008 ELECTRIC - CONSTRUCTION POWER RJIROUDE Approved IVRS - Inspection :*
03/19/2008 ELECTRIC - CABLE DROP RJIROUDE Approved IVRS - Inspection :*
04/01/2008 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
GAS CARD AT METER
PLEASE CALL IN ALL UNAPPROVED INSPECTIONS FOR PLUMBING PRIOR TO FINAL
04/01/2008 PLUMBING - GAS PRESS TEST FNL RRICH Approved IVRS - Inspection :*
04/02/2008 U VALUE FOR WINDOW GDABBS Approved IVRS - Inspection :*
04/02/2008 BUILDING ABOVE CEILING GDABBS Approved IVRS - Inspection :*
05/14/2008 PLUMBING - SEWER HCS CONNECT RRICH Approved IVRS - Inspection :*
06/12/2008 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
06/12/2008 MECHANICAL - PROGRESS JMILITEL Approved
06/12/2008 MECHANICAL - ABOVE CEILING JMILITEL Approved
06/20/2008 SEWER - PRE CONSTRUCTION MTG RRICH Approved
06/20/2008 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
RECEIVED BACTERIA REPORT FOR POTABLE WATER
06/20/2008 PLUMBING - PROGRESS RRICH Approved IVRS - Inspection :*
06/23/2008 ELECTRIC - FINAL RJIROUDE Approved IVRS - Inspection :*
06/23/2008 OUTDOOR LIGHTING FINAL RJIROUDE Approved IVRS - Inspection :*
06/24/2008 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
06/24/2008 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
06/24/2008 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
06/24/2008 FIRE SPKLR - FINAL LTHOMAS Approved
06/24/2008 FIRE - ALARM FINAL LTHOMAS Approved
06/24/2008 FIRE - FINAL LTHOMAS Approved
06/25/2008 BUILDING - FINAL GDABBS Approved IVRS - Inspection :*
06/25/2008 BUILDING - PROGRESS GDABBS Approved IVRS - Inspection :*
06/25/2008 FRAMING GDABBS Approved IVRS - Inspection :*
06/27/2008 SIGN - FINAL JSONKIN Approved IVRS - Inspection :*
07/01/2008 RIGHT OF WAY - FINAL RLEIGH Approved PER EMAIL
07/10/2008 ENGINEERING - FINAL JBRUCKME Approved PROVIDE BARRICADING TO EXCLUDE PUBLICE ACCESS FROM ALL AREAS WHERE ON-GOING CONSTRUCTION ACTIVITY IS OCCURRING.