Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06CM04373
Permit Details
Apply Date:
07/27/2006
Applicant:
VLADIMIR ZILBERMAN
Description:
TI:RESTAURANT (1ST TENANT IN SHELL)
Architects:
- WINDLE, DAVID SCOTT
Contractors:
- CANYON BUILDING AND DESIGN L L C
Permit Reviews
Permit Number - T06CM04373
Permit Status: C of o
Permit Description: TI:RESTAURANT (1ST TENANT IN SHELL)
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
07/27/2006 | PLANS OK TO SUBMIT - 3RD PARTY | 07/27/2006 | COMPLETED |
07/27/2006 | 3RD PARTY REVIEW-COMMERCIAL TI | 09/27/2006 | COMPLETED |
09/27/2006 | POST 3RD PARTY REVIEW | 10/13/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM04373
Permit Status: C of o
Permit Description: TI:RESTAURANT (1ST TENANT IN SHELL)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/27/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T06CM04373
Permit Description: TI:RESTAURANT (1ST TENANT IN SHELL)
Total Completed Inspections - 33
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2006 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* 1. GREASE WASTE REDLINE ON SITE. 2. OK TO COVER SUBJECT TO ARCHITECTS APPROVAL OF REDLINE |
11/01/2006 | BUILDING PRE-SLAB | JBURGE | Approved | IVRS - Inspection :* OK TO POUR |
11/01/2006 | EXCAVATION/LAYOUT REBAR & ZON | JBURGE | Approved | IVRS - Inspection :* |
11/02/2006 | PLUMBING - PRE SLAB | RMYERS | Approved | IVRS - Inspection :* OK FOR CONCRETE |
11/17/2006 | FRAMING | GDABBS | Approved | IVRS - Inspection :* |
11/17/2006 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* |
11/21/2006 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
11/22/2006 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* 1) OK FOR SHEETROCK |
12/10/2006 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* 1. GAS PRESSURE TEST OK 2. REDLINES AS BUILTS OK |
12/14/2006 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
12/14/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED FOR #101 PER C. CLEMENS |
12/18/2006 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* |
12/19/2006 | PLUMBING - GAS PRESS TEST FNL | RRICH | Approved | IVRS - Inspection :* 1. SHALL TERMINATE WATER HEATER T&P DRAIN PROPERLY PRIOR TO ENERGIZE. 2. SHALL SECURE SAFETY CABLES AT APPLIANCES. |
12/20/2006 | MECHANICAL - HOODS | JMILITEL | Approved | IVRS - Inspection :* RELOCATE DUCT SMOKE DETECTOR TO AN ACCESSIBLE LOCATION. PROVIDE AUDIBLE & VISIBLE ALARMS. CHECKED ACCESS DOORS OK FOR CEILING TILES. |
12/20/2006 | SIGN - FINAL | JYBARRA | Approved | TEMP C/O; MUST FINAL ELEC ON T06OT02304 BEFORE FINAL C/O CAN BE ISSUED |
12/21/2006 | RIGHT OF WAY - FINAL | MOTERO | Approved | |
12/21/2006 | NPPO - FINAL | ACONNOR | Approved | |
12/21/2006 | LANDSCAPE - FINAL | ACONNOR | Approved | OK for Temp. C of O Approval when shell comments and concerns are addressed. |
12/21/2006 | ELECTRIC - TEMP POWER FOR TEST | RHOLLAND | Approved | 1. DERATE CONDUCTORS PER 310.15 2. BREAKERS NOT AS PER PLANS 3. PLANS ARE TO BE REVISED 4. PANEL KB FEEDERS PASSING THROUGH PANEL KA 5. SECURE CONDUIT TO PANEL KB AND TIGHTEN LOOSE FITTINGS. |
12/21/2006 | FIRE SPKLR - FINAL | LLAKEY | Approved | |
12/22/2006 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* |
12/22/2006 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* |
12/27/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* CAME BACK. CORRECTIONS HAVE BEEN MADE OK FOR FINAL |
12/27/2006 | FIRE - FINAL | CSCHULTZ | Approved | |
12/27/2006 | HEALTH DEPT - FINAL 724-7908 | RPEYTON | Approved | |
12/27/2006 | FIRE - KITCHEN EXH HOOD FINAL | CSCHULTZ | Approved | |
12/27/2006 | ELECTRIC - ABOVE CEILING | RMAJUTA | Approved | |
12/27/2006 | ENGINEERING - FINAL | MRUSSO | Approved | PER SHELL BUILDING |
12/27/2006 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection :* 1. CORRECT PNL SCH MP - OK 2. SEAL IO HOLE IN GUTTER ABOVE MP - OK |
12/27/2006 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* |
12/28/2006 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* UNABLE TO FINAL TI, UNTIL SHELL HAS BEEN FINALED |
01/04/2007 | MECHANICAL - HOOD SYSTEMS | JMILITEL | Approved | |
03/07/2007 | PERMIT FINALED | LJACKSON | Approved |