Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2007 | MECHANICAL - FINAL | Approved | ||
| 12/27/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CAME BACK. CORRECTIONS HAVE BEEN MADE OK FOR FINAL |
|
| 12/22/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS. OK TO FILE FOR TEMP C OF O |
|
| 12/21/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PAINT EXPOSED BLACK IRON ON ROOF. BE SURE SCRUBBER IS INTERLOCKED WITH EXHAUST FAN. WHERE IS FIRE SUPPRESSION SUPPLY FOR SCRUBBER NEED TO SEE DETERGENT TANK AS PER PLANS NEED TO TEST DUCT SMOKE DETECTORS. PROVIDE A TEST ON SCRUBBER. |