Permit: T06CM04373

Parcel: 12510004B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04373

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/27/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. CORRECT PNL SCH MP - OK
2. SEAL IO HOLE IN GUTTER ABOVE MP - OK
12/20/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION ONLY
1. ALL LOW VOLTAGE WIRING TO BE RAN IN A NEAT AND WORKMAN LIKE MANNER WITH INDIVIDUAL SUPPORTS AND FOLLOW BUILDING SURFACE, WIRING NOT ALLOWED ON GRID, PROVIDE GROUND FOR ALARM PANEL.
2. EMERGENCY LIGHTING NOT COMPLETE/NOT INSPECTED @ THIS POINT
3. CONDUCTORS IN GUTTERS TO BE DERATED PER NEC 366.6
4. INSTALL FINISHED PANEL DIRECTORY AND MAKE SURE THEY ARE CORRECT -- NEC 408.4
5. J-BOXES CHECK BOX FILL NEC 314.16, PROPERLY GROUND NEC 250.314
6. PROPERLY SECURE/SUPPORT MC - NEC 330.30
7. WIRING INCOMPLETE ABOVE CEILING
8. KITCHEN RECEPTACLES NEED GFI PROTECTION EXCEPT WHERE YOU HAVE SINGLE RECEPTACLE FOR APPLIANCE -
NEC 210.8 B
9. HOOD MISSING BULBS AND INTERLOCK/SWITCH NOT WIRED CORRECTLY.
12/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/15/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NO POWER
2. FINISH CEILING WORK
3. SUPPORT VDV CABELING 725.6 & 800.6 & 300.11
4. EXTENDER RINGS NEEDED AT COMBUSTIBLES OR MORE THAN 1/4" NON-COMBUSTIBLE 314.20
5. ABOVE WALK-IN USE APPROVED FITTING WITH ENT AND SEAL WITH NON-COMBUSTABLE 300.7
6. FINISH ALL PANELS.