Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
3939 N 1ST AV
Address NEW:
3939 N 1ST AV
Apply Date:
06/08/2006
Applicant:
ARCHITECTURAL DESIGN GROUP INC
Description:
TI: PAWN SHOP
Architects:
  • ARCHITECTURAL DESIGN GROUP INC
Contractors:
  • DIVISION II CONSTRUCTION COMPANY

Permit Reviews

Permit Number - T06CM03421
Permit Status: Expired
Permit Description: TI: PAWN SHOP
Start Date Submittal Complete Date Status  
06/08/2006 PLANS OK TO SUBMIT - 3RD PARTY 06/09/2006 COMPLETED Review Details
06/09/2006 3RD PARTY REVIEW-COMMERCIAL TI 06/27/2006 COMPLETED Review Details
06/27/2006 POST 3RD PARTY REVIEW 06/29/2006 COMPLETED Review Details
07/03/2006 RESUBMITTAL 07/05/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM03421
Permit Status: Expired
Permit Description: TI: PAWN SHOP
Total Outstanding Activity Conditions - 3
Date Name
06/08/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.
06/27/2006 SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED.
06/27/2006 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06CM03421
Permite Description: TI: PAWN SHOP
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
12/04/2006 BUILDING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 12" ADDRESS DISPLAY REQUIRED PER PCZO AT FRONT OF BUILDING.
2. NON-ACCESSIBLE THRESHOLDS AT RESTROOMS AND PATH TO RESTROOM (MUST COMPLY WITH ANSI 117.1)
3. MUST PROVIDE NON-PERMEABLE WALL SURFACE BEHIND W.C'S
4. NOTE: MOBILE MINI INSTALLED ON SOUTHSIDE MUST BE APPROVED BY ZONING & ENGINEERING.
12/04/2006 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/04/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY PANEL "B" DISCONNECT & PROPERLY GROUND IT
2. REIDENTIFY PANEL "A" DIRECTORY
3. REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK
4. CORRECTLY IDENTIFY PANEL "B" PANEL DIRECTORY AND STRAP FEEDER EMT WITHIN 3' OF PANEL.
5. MAX 20 AMP OVERCURRENT ON INSTA-HOTS, STRAP FLEX AND DISCONNECT TO DISCONNECT ALL HOTS - 2 POLE SWITCH?
6. STORAGE ROOM EMERGENCY LIGHT NOT WORKING AND IS BLOCKED BY STORAGE RACK.
7. TIGHTEN LOOSE DEVICES, REPLACE CRACKED PLATES
8. MAX 360 DEG. IN RACEWAYS -- BOX TO PANEL
9. PROVIDE ACCESS TO J-BOX
10. GROUND ALL J-BOXES SHEET METAL SCREWS NOT ALLOWED.
12/04/2006 SIGN - FINAL N/A Partial Approval IVRS - Inspection :*TEMP C/O; MUST FINAL ELEC ON TO6OT02140 AND MUST PERMIT OR REMOVE BANNER ON DF

Completed Inspections

Permit Status: Expired
Permit Number: T06CM03421
Permit Description: TI: PAWN SHOP
Total Completed Inspections - 17
Date Description Inspector Results Comments
07/26/2006 FRAMING AQUIROZ Approved IVRS - Inspection :*
EXCLUDES RESTROOM
07/26/2006 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
08/23/2006 EXT METAL CLIPS/EXT SHEATHING AQUIROZ Approved IVRS - Inspection :*
08/30/2006 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection :*
09/19/2006 STUCCO MESH AQUIROZ Approved IVRS - Inspection :*
10/31/2006 PLUMBING - ROUGH, SOIL RLEDONNE Approved IVRS - Inspection :*
11/08/2006 ELECTRIC - CABLE DROP IVR USER Approved IVRS - AP canceled
11/14/2006 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
11/14/2006 PLUMBING - PRE SLAB RMYERS Approved IVRS - Inspection :*
11/17/2006 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
12/04/2006 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
12/04/2006 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
OK FOR FINAL
12/04/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
12/04/2006 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
12/04/2006 FIRE - FINAL LTHOMAS Approved
12/04/2006 NPPO - FINAL ACONNOR Approved
12/04/2006 LANDSCAPE - FINAL ACONNOR Approved

Documents

File Name Document Type  
T06CM03421 2025 MASS-UPLOAD.PDF DOCUMENTS VIEW
3421-01-0001-01-0001.TIF CONSTRPLANS VIEW
3421-01-0001-01-0002.TIF CONSTRPLANS VIEW
3421-01-0001-01-0003.TIF CONSTRPLANS VIEW
3421-01-0001-01-0004.TIF CONSTRPLANS VIEW
3421-01-0001-01-0005.TIF CONSTRPLANS VIEW
3421-01-0001-01-0006.TIF CONSTRPLANS VIEW
3421-01-0001-01-0007.TIF CONSTRPLANS VIEW
3421-01-0001-01-0008.TIF CONSTRPLANS VIEW
3421-01-0001-01-0009.TIF CONSTRPLANS VIEW
3421-01-0001-01-0010.TIF CONSTRPLANS VIEW
3421-01-0001-01-0011.TIF CONSTRPLANS VIEW
3421-01-0001-01-0012.TIF CONSTRPLANS VIEW
3421-01-0001-01-0013.TIF CONSTRPLANS VIEW