Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 11/09/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BRACE RECEPTACLE BOX FOR BACK SUPPORT OK WALL COVER BATHROOM AREAS (BOTH) AFTER CORRECTION. |
|
| 08/24/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN CEILING STILL NEED TO CORRECT #5 & #6 FROM PREVIOUS INSPECTION. NOTE: INSTALL ALL J-BOX COVERS |
|
| 08/23/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE BOX EXTENSION FOR ALL OVERFILLED BOXES AS REQUIRED BY NEC 314.16 2. USE EQUIPMENT GROUND TO GROUND ALL METAL ENCLOSURES - NEC 250 3. DEMO ALL OLD LIGHTING TO BE REMOVED ABOVE CEILING. 4. INSTALL ALL SLACK WIRES FOR FIXTURES. 5. USE AN APPROVED METHOD SUCH AS STRUT AND CLAMPS TO SUPPORT EMT -- NEC 358.12(5) 6. SUPPORT EMT PER NEC 358.30 |
|
| 07/26/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN INTERIOR WALLS OK TO COVER FLOOR RECEPT RACEWAYS *NOTE: EXTEND BOX ON NORTH WALL TO FINISHED SURFACE SO A BLANK COVER CAN BE INSTALLED. |