Permit: T06CM03421

Parcel: 10601004B


Addresses:

3939 N 1ST AV

Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/04/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
11/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BRACE RECEPTACLE BOX FOR BACK SUPPORT
OK WALL COVER BATHROOM AREAS (BOTH) AFTER CORRECTION.
08/24/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN CEILING STILL NEED TO CORRECT #5 & #6 FROM PREVIOUS INSPECTION.
NOTE: INSTALL ALL J-BOX COVERS
08/23/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE BOX EXTENSION FOR ALL OVERFILLED BOXES AS REQUIRED BY NEC 314.16
2. USE EQUIPMENT GROUND TO GROUND ALL METAL ENCLOSURES - NEC 250
3. DEMO ALL OLD LIGHTING TO BE REMOVED ABOVE CEILING.
4. INSTALL ALL SLACK WIRES FOR FIXTURES.
5. USE AN APPROVED METHOD SUCH AS STRUT AND CLAMPS TO SUPPORT EMT -- NEC 358.12(5)
6. SUPPORT EMT PER NEC 358.30
07/26/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN INTERIOR WALLS
OK TO COVER FLOOR RECEPT RACEWAYS
*NOTE: EXTEND BOX ON NORTH WALL TO FINISHED SURFACE SO A BLANK COVER CAN BE INSTALLED.