Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY PANEL "B" DISCONNECT & PROPERLY GROUND IT 2. REIDENTIFY PANEL "A" DIRECTORY 3. REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK 4. CORRECTLY IDENTIFY PANEL "B" PANEL DIRECTORY AND STRAP FEEDER EMT WITHIN 3' OF PANEL. 5. MAX 20 AMP OVERCURRENT ON INSTA-HOTS, STRAP FLEX AND DISCONNECT TO DISCONNECT ALL HOTS - 2 POLE SWITCH? 6. STORAGE ROOM EMERGENCY LIGHT NOT WORKING AND IS BLOCKED BY STORAGE RACK. 7. TIGHTEN LOOSE DEVICES, REPLACE CRACKED PLATES 8. MAX 360 DEG. IN RACEWAYS -- BOX TO PANEL 9. PROVIDE ACCESS TO J-BOX 10. GROUND ALL J-BOXES SHEET METAL SCREWS NOT ALLOWED. |