Permit: T06CM03421

Parcel: 10601004B


Addresses:

3939 N 1ST AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY PANEL "B" DISCONNECT & PROPERLY GROUND IT
2. REIDENTIFY PANEL "A" DIRECTORY
3. REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK
4. CORRECTLY IDENTIFY PANEL "B" PANEL DIRECTORY AND STRAP FEEDER EMT WITHIN 3' OF PANEL.
5. MAX 20 AMP OVERCURRENT ON INSTA-HOTS, STRAP FLEX AND DISCONNECT TO DISCONNECT ALL HOTS - 2 POLE SWITCH?
6. STORAGE ROOM EMERGENCY LIGHT NOT WORKING AND IS BLOCKED BY STORAGE RACK.
7. TIGHTEN LOOSE DEVICES, REPLACE CRACKED PLATES
8. MAX 360 DEG. IN RACEWAYS -- BOX TO PANEL
9. PROVIDE ACCESS TO J-BOX
10. GROUND ALL J-BOXES SHEET METAL SCREWS NOT ALLOWED.